GalxC~Cool~Flo® Product
|
Application
|
Pack Size
|
Dose
Rate
|
Further
Comments
|
|
GalxC~Cool~Flo LV
|
Frost, corrosion and scale protection for food systems (non-direct contact) Environmentally Friendly
|
20 ltr, 215 ltr & 1,000kg IBC’s
|
According to freeze protection required but minimum of 20% system volume
|
Green coloured heat transfer fluid.
|
|
GalxC~Cool~Flo ME
|
Frost, corrosion and scale protection for non- food systems.
|
20 ltr, 215 ltr & 1,000kg IBC’s
|
According to freeze protection required but min’ of 20% of system volume
|
Red coloured heat transfer fluid.
|
|
GalxC~Cool~Flo LC15
|
Used in very low conductivity systems i.e. plasma welding
|
25 kg, 200kg 1,000kg IBC’s
|
Please call tech’ helpdesk for further details 01398-331078
|
Very low conductivity with corrosion protection. Used where electrical conductivity can cause problems.
|
|
GalxC~Cool~Flo ENV
|
Environmentally acceptable, non-toxic heat transfer fluid especially for sensitive food industry use
|
25 litre, 200 litre & 1,000 litre IBC’s
|
Please call tech’ helpdesk for further details 0845 094 2644
|
Biodegradeable, non-toxic, good anti-corrosion properties. Especially good for sensitive food applications.
|
|
GalxC~Cool~Flo LF27
|
Concentrated
anti-corrosion & scale protection for water circuits above 0°C
|
5 litres
25 kg, 200kg
|
2% of system volume. Send sample for test after dosing.
|
Concentrate used in systems where frost protection is not necessary but scale/corrosion protection is required.
|
|
GalxC~Cool~Flo M75
|
Concentrated Non-foaming biocide to prevent microbiological growths in closed water systems
|
5 litres 25 kg, 200kg
|
150 – 300 ppm this means
1.5 –3.0 mls per 10 litres of water in the system
|
Broad spectrum, non-foaming biocide used to kill microbiological growths in non-food systems. Use in large systems.
|
|
GalxC~Cool~Flo B99
|
Clean-up polymer for flushing water systems. Also used as an anti-scale booster in hard water systems
|
25 kg, 200kg
|
2.5 to 5.0 litres per m3 of water in system, or 250 –500mls
per 100 ltrs of system volume
|
This polymer will aid flushing of new and old systems and can be used as a booster to stop scale build-up. Generally used in non-food systems.
|
|
Cleaner used in heavily fouled systems for removing rust, millscale and greases. Can be used in conjunction with B99.
|
25 kg, 200kg
|
1 – 2 % of system volume. Call tech helpdesk for appropriate cleaning method
|
This cleaner should be used in accordance with directions from the water helpdesk. Dosage and application can vary depending on the problem. Water analysis will give indications of necessary action to take.
|
Hydro~V Sterilizers
|
For controlling micro-biological growths in food systems where chemicals cannot be used
|
Unit attached to chiller system
|
See operation manual
|
Hydro~V used to control microbiological growths by passing all/part of the recirculating water over sterilizer to systems settings.
|
|
Demineralised Water
|
Pure water for diluting Cool~Flo products in chilled water systems
|
20 ltr, 215 ltr & 1,000kg IBC’s
|
Used to dilute products and fill systems.
|
Recommended where tap water is hard, or if there is stainless steel in the system and/or high levels of chloride (CI-) ions
|